These maximums use the stored XHHW / XHHW-2 conductor area and the implemented 40% multi-conductor fill limit. The full table compares every raceway size that fits at least one conductor.
Maximum counts are computed for every stored raceway and trade-size combination at 40% fill. Combinations below one conductor are omitted.
| Raceway | Trade size | Raceway area | Maximum at 40% |
|---|---|---|---|
| EMT | 2″ | 3.356 in² | 2 |
| EMT | 3″ | 8.846 in² | 6 |
| EMT | 4″ | 14.753 in² | 11 |
| EMT | 1-1/4″ | 1.496 in² | 1 |
| EMT | 1-1/2″ | 2.036 in² | 1 |
| EMT | 2-1/2″ | 5.858 in² | 4 |
| EMT | 3-1/2″ | 11.545 in² | 8 |
| PVC Schedule 40 | 2″ | 3.291 in² | 2 |
| PVC Schedule 40 | 3″ | 7.268 in² | 5 |
| PVC Schedule 40 | 4″ | 12.554 in² | 9 |
| PVC Schedule 40 | 1-1/4″ | 1.453 in² | 1 |
| PVC Schedule 40 | 1-1/2″ | 1.986 in² | 1 |
| PVC Schedule 40 | 2-1/2″ | 4.695 in² | 3 |
| PVC Schedule 80 | 2″ | 2.874 in² | 2 |
| PVC Schedule 80 | 3″ | 6.442 in² | 4 |
| PVC Schedule 80 | 4″ | 11.258 in² | 8 |
| PVC Schedule 80 | 1-1/2″ | 1.711 in² | 1 |
| PVC Schedule 80 | 2-1/2″ | 4.119 in² | 3 |
| Rigid metal conduit (RMC) | 2″ | 3.408 in² | 2 |
| Rigid metal conduit (RMC) | 3″ | 7.499 in² | 5 |
| Rigid metal conduit (RMC) | 4″ | 12.882 in² | 9 |
| Rigid metal conduit (RMC) | 1-1/4″ | 1.526 in² | 1 |
| Rigid metal conduit (RMC) | 1-1/2″ | 2.071 in² | 1 |
| Rigid metal conduit (RMC) | 2-1/2″ | 4.866 in² | 3 |
| Intermediate metal conduit (IMC) | 2″ | 3.630 in² | 2 |
| Intermediate metal conduit (IMC) | 3″ | 7.922 in² | 6 |
| Intermediate metal conduit (IMC) | 4″ | 13.671 in² | 10 |
| Intermediate metal conduit (IMC) | 1-1/4″ | 1.647 in² | 1 |
| Intermediate metal conduit (IMC) | 1-1/2″ | 2.225 in² | 1 |
| Intermediate metal conduit (IMC) | 2-1/2″ | 5.135 in² | 3 |
| ENT flexible nonmetallic | 2″ | 3.291 in² | 2 |
| ENT flexible nonmetallic | 1-1/4″ | 1.453 in² | 1 |
| ENT flexible nonmetallic | 1-1/2″ | 1.986 in² | 1 |
The existing conduit-fill calculator is preset to this conductor, wire size, and 3/4-inch EMT. Choose any raceway, trade size, or conductor count to check a run.
0 conductors fit at the 40% fill limit using the stored 0.5166 square-inch conductor area.
0 conductors fit at 40% fill. A value of 0 means one conductor of this size exceeds the 40% multi-conductor table capacity for that raceway size.
Each conductor uses the stored 0.5166 square-inch area. Applying that value across the available raceway areas produces 33 raceway-size rows that fit at least one conductor at 40%.